Line 11: Line 11:
 After changing protocol type, it neccessary to re-power the drive. Also, with changing protocol 8-30 [0] FC to Modbus [2] the baud reat will be automatically changed too (9600 for FC51 and 19200 for Modbus).  After changing protocol type, it neccessary to re-power the drive. Also, with changing protocol 8-30 [0] FC to Modbus [2] the baud reat will be automatically changed too (9600 for FC51 and 19200 for Modbus). 
  
-Преобразователем можно управлять по Modbus только когда он переведен из режима Hand (ручное или местное управление) в Auto (дистанционное) +The drive can only be controll via Modbus when it is switched from Hand to Auto mode.
-При задании частоты по интерфейсу может быть ситуация, когда фактическая величина скорости вращения будет постоянно отличаться от заданной на какое-то смещение. Такое может быть если у преобразователя частоты задано несколько источников частоты (485, аналоговый вход, дискретные клеммы и др. ), которые он может например складывать. +
-Управление приводом производится через:+
  
-слово управления (CTW) - пускстопвыбор конфигурации и дрОно доступно по адресам C0..C15 через функцию Read coils, либо HR49999 через функцию чтения holding register +There might be a case, when actual frequency differs from the setpoint by a certain level.  This is possible when there are many source frequency inputs enabled (485, analog input, digital inputand they summed together.  
-задание частоты через Bus reference register (REF) по адресу HR50009 + 
-контроль состояния - через слово статуса STW - C32..C47 , либо HR50199 +The drive is controled and monitored via: 
-фактическая частота вращения (MAV) по адресу HR50209. + 
-Подробно работа с ПЧ Danfoss описана в документе MG.02.A4.02 VLT® Micro Drive FC 51 Operating Instructions. Ниже приведена таблица с параметрамиНомера параметров, указанные в этих таблицах, необходимо указывать в настройках регистра со смещением -1. Например, Bus reference register (REF) в документации имеет адрес 50000, но в запросе modbus он будет в виде 49999 (HR49999 в настройках регистров WebHMI)+  ***CTW** control word startstopconfiguration etcaccessible bitwise on C0..C15 addresses with Read coils or HR49999 with holding register read 
 +  ***REF** Bus reference register - frequency setpoint HR50009 
 +  ***STW** status word accessible bitwise on C32..C47 addresses with Read coils or HR50199 with holding register read 
 +  **MAV** actual frequency HR50209. 
 + 
 +More details on working with Danfoss FC drives are described in document MG.02.A4.02 VLT® Micro Drive FC 51 Operating Instructions. Below is a table with parametersThe parameter numbers specified in these tables must be specified in the register settings with an offset of -1. For examplethe Bus reference register (REF) in the documentation has the address 50000, but in the WebHMI you set it as HR49999.
  
 {{::fc51_memory_map.png?direct}} {{::fc51_memory_map.png?direct}}
  
-Для модификации произвольного параметра преобразователя частоты, необходимо использовать формулу - (Pr.Num. * 10 - 1). Например, параметр 8-31 (сетевой адресбудет иметь адрес 831*10 - 1 = 8309.+To access any paramter you can use the formula: (Pr.Num. * 10 - 1). E.g. 8-31 (bus addresswill equal 831*10 - 1 = 8309.
  
 {{ ::fc51_reg_setup_1.png?direct&600 |}} {{ ::fc51_reg_setup_1.png?direct&600 |}}
  
-Ниже приведены настройки регистров для управления преобразователем частоты VLT Micro drive FC51 - пуск остановсмена направления вращениязадание частоты вращения.+Below are the register settings for controlling the VLT Micro drive FC51 frequency converter start stopchange of direction of rotationspeed reference. 
 {{ ::fc51_reg_setup_2.png?direct&600 |}} {{ ::fc51_reg_setup_2.png?direct&600 |}}
  
-В частотном преобразователе значения частоты представлены следующим образом - частоте 50Гц (100% шкалысоответствует число 16384. Отрицательным значениям - тоже число в двоичном дополненном виде (two's complement). Поэтому для правильного отображения частоты и ее задания для регистров необходимо использовать множитель 50/16384 = 0.0030517578125, и указывать соответствующий формат в свойствах регистра+In the frequency converter, the frequency values are presented as follows: the frequency 50 Hz (100% of the scalecorresponds to the number 16384. Negative values are also a number in binary complementary form (two's complement). Therefore, to correctly display the frequency and its task for the registers, it is necessary to use the multiplier 50/16384 = 0.0030517578125, and specify the appropriate format in the register properties.
  
 По [[ https://www.youtube.com/watch?v=iU3dzC1dQ4E | ссылке ]] доступно видео (in Russian language) с демонстрацией управления частотным приводом Danfoss, а также управление холодильным контроллером Danfoss AK-CC 550. По [[ https://www.youtube.com/watch?v=iU3dzC1dQ4E | ссылке ]] доступно видео (in Russian language) с демонстрацией управления частотным приводом Danfoss, а также управление холодильным контроллером Danfoss AK-CC 550.