Control for the Owen frequency drive
The example will be given for the PCHV-2 vector frequency drive.
The parameters to be set:
- 8-01 = 2 (source of control CTW only)
- 8-02 = 1 (source of CTW is from RS-485)
- 8-04 = 0 (disable comm. timeout)
- 8-30 = 2 (Modbus RTU protocol selection)
- 8-31 = 1 (slaveId)
- 8-32 = 2 (9600 comm. speed)
- 8-33 = 2 (no parity, one stop bit)