User Tools

Site Tools


owen-pchv

This is an old revision of the document!


Control for the Owen frequency drive

The example will be given for the PCHV-2 vector frequency drive.

The parameters to be set:

  • 8-01 = 2 (source of control CTW only)
  • 8-02 = 1 (source of CTW is from RS-485)
  • 8-04 = 0 (disable comm. timeout)
  • 8-30 = 2 (Modbus RTU protocol selection)
  • 8-31 = 1 (slaveId)
  • 8-32 = 2 (9600 comm. speed)
  • 8-33 = 2 (no parity, one stop bit)
owen-pchv.1713343214.txt.gz ยท Last modified: 2024/04/17 08:40 by emozolyak

Donate Powered by PHP Valid HTML5 Valid CSS Driven by DokuWiki