Line 6: Line 6:
  
 The parameters to be set:  The parameters to be set: 
-  * 8-01 = 2 (source of control CTW only) +  * 8-01 = 2 (source of control CTW only)  default is 0  
-  * 8-02 = 1 (source of CTW is from RS-485)+  * 8-02 = 1 (source of CTW is from RS-485) 
   * 8-04 = 0 (disable comm. timeout)   * 8-04 = 0 (disable comm. timeout)
-  * 8-30 = 2 (Modbus RTU protocol selection)+  * 8-30 = 2 (Modbus RTU protocol selection) 
   * 8-31 = 1 (slaveId)   * 8-31 = 1 (slaveId)
-  * 8-32 = 2 (9600 comm. speed) +  * 8-32 = 2 (9600 comm. speed)            default is 3 (19200
-  * 8-33 = 2 (no parity, one stop bit)+  * 8-33 = 2 (no parity, one stop bit)     default is 0 even parity 
  
 To save the parameters to EEPROM the 64 (decimal) register should be in 1.  To save the parameters to EEPROM the 64 (decimal) register should be in 1. 