Frequently Asked Questions (FAQ)
Screens, Dashboard visualization
Screen text widget
Colorizing register values into custom colours
Question: In my screen widget I want the register values have custom colour. I set a color for them, but still they are black/white colours (depending on theme)
The register values in the WebHMI are colourized using this rule - it is either default value color, or the color defined in the register STATE. There is a default register value style which overrides text widget styles for values. So, to make your register value of a desired colour, set a STATE for the register with the colour you want.
Performance issues
My WebHMI is slow
There are many reasons why your device may slow down, a “disable function & try” method should be applied to detect the source of this problem.
Below a summary of the possible causes is provided:
Screens / Dashboards
- Use screens wherever is possible for visualisation, and use dashboards as a part of screens for graphic part, which can not be done with the screens.
- Avoid using bulky DASHBOARDS (too rich in elements, having heavy-weight pictures , trends with long time window etc. ) , normal dashboard is about tens of KB, not MB!
- Set appropriate refresh time in the settings.
- Keep the number of open tabs minimal for the current sessions. If you need multiple tabs, use auto-close session checkbox to prevent unattended access.
Scripts
- Avoid using many scripts (like dashboards scripts or upon change value scripts). The better way is using a few big scripts or scripts with libraries instead of a lot of small scripts (each script takes some os environment)
- Run scripts upon changing value, minimize the number of scripts, running in each scan
- Minimize “WriteReg” Lua instructions in each scan. It is better to use wrapping function UpdReg(), which writes to register only if value has changed.
Communication
- Group register to read on external device and use group reading.
- Decrease timeout and tries in external connections if it possible. Use auto-drop&try for not available connections.
- Organize and set different reading periods for variables.
- Keep the actual T1 time less than system scan set in the settings. this will give more “room” for OS' background processes.
Writing to log
- Minimize logging many registers to DB,
- Set appropriate log speed for the registers.check you don't have many events logged each scan.
Development process
- Keep the number of registers in the project below 2-3K
- During development, keep track of the Load Average parameter it should be below 1 (but can have short bursts above this value, which ought to fall soon)
- Avoid making simultaneous changes at once, like turning OFF-ON many regs, connection, scripts etc. Use save & apply feature of the latest fw. (apply all changes at once, instead of creating a queue for changes..)
- In the comm. log, you can set TRACE level and see what times each operation takes (each connection, script, communication with device etc.), checking timestamps