User Tools

Site Tools


connectors

This is an old revision of the document!


External connectors

10-pin terminal connector

Pin Description
1 Common 24V
2 “+” line of 24V
3 Isolated gnd for LAN/WAN cable shields
4 Relay #1 N.O.
5 Common wire for relays #1,2
6 Relay #2 N.O.
7 N.C.
8 RS-485 signal ground
9 Data- (:B) RS-485
10 Data+ (:A) RS-485

Switching capacity for SSRs - max. current 100мА ~/=, max. voltage - up to 350V.

When using shielded Ethernet cable its shield will connect to GND terminal, which in his turn recommended to wire to ground for better noise protection.

Voltage input 24V +/- 10% (15%).

RS-485

WiFi

Connection of external WiFi antenna (RP-SMA type)

USB

It is possible to connect various USB devices like RS-485, RS-232 ports, USB hubs, 3G and 4G modems, etc. Max load is 5V 500mA.

LAN and WAN

connectors.1531218977.txt.gz · Last modified: 2018/07/10 10:36 by akuzmuk