====== Connecting AirPoint - M (metering) to WebHMI ====== This version of the AirPoint module is intended for reading data from heat meters via the M-bus protocol and transmitting telemetry data via the MQTT protocol to data collection systems. {{ :conn:conn-examples:ap-m-app-structure2.png?direct&600 |}} ===== Features ===== *Compatible meters: DIEHL Scylar INT, Siemens FUE950, Danfoss Infocal, and their equivalents *Connection using a standard connector (included with the module) instead of the communication board of the heat meter *Energy saving polling cycle {{ :conn:conn-examples:scylar-picutre.png?direct&350 |}} ===== Connection method ===== The module connects to a meter with edge connector right to the extension module slot. {{ ::metering_option.jpg?direct&400 |}} ==== M-bus protocol ==== All meters are read with "REQ-UD2" request using broadcast address. The M-bus tags are mapped onto statndard AirPoint's MQTT topics: ^ Value ^ Description ^ Units ^ Mapped to ^ |FWT | Forward temp. | °C | "temp_int" | |RET | Return temp. | °C | "temp_ext" | |E | Energy | Gcal| "counter_in1" | |VOL | Volume | m3 | "counter_in2" | |Q | Flow | m3/hour | "hum_int" | === Connection with Sontex SuperCalc531 === The AirPoint - M can be connected to the heatmeter w/o extra communication module. {{ ::7bit:sontex-supercalc-531-rev1.png?direct&600 |}} === Connection with PolluTherm X === The AirPoint - M can be connected to the heatmeter w/o extra communication module. {{ :7bit:sensus-pollutherm_-_rev1.png?direct&600 |}}