synapse
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revisionNext revision | Previous revisionNext revisionBoth sides next revision | ||
synapse [2019/01/04 12:27] – [Modbus registers map] emozolyak | synapse [2021/07/20 13:56] – [Modbus registers map] emozolyak | ||
---|---|---|---|
Line 1: | Line 1: | ||
====== Synapse remote I/O module ====== | ====== Synapse remote I/O module ====== | ||
- | {{ ::synapse_small.png? | + | {{ ::syn_1wire.jpg? |
The Synapse module (further reffered to as ' | The Synapse module (further reffered to as ' | ||
- | The module has 2 Ethernet interfaces (working in a " | + | The module has 2 Ethernet interfaces (working in a " |
+ | & MQTT protocols**. The enclosure is for panel / DIN 35 mm mount. | ||
==== Specifications ==== | ==== Specifications ==== | ||
Line 15: | Line 16: | ||
|Counter inputs (non-volitile) | 8 (digital inputs can be counting inputs with max. frequency of 1kHz, with anti-jitter filter of a 1ms step ) | | |Counter inputs (non-volitile) | 8 (digital inputs can be counting inputs with max. frequency of 1kHz, with anti-jitter filter of a 1ms step ) | | ||
|Digital Outputs| (2 groups x 4 outputs (symistor or relay ))2A | | |Digital Outputs| (2 groups x 4 outputs (symistor or relay ))2A | | ||
- | |1Wire bus | up to 32 sensors, cable length up tup 200 мeters | | + | |1Wire bus | up to 32 sensors, cable length up to 200 мeters | |
|Power supply for 'dry contacts' | |Power supply for 'dry contacts' | ||
|Enclosure protection | IP40 | | |Enclosure protection | IP40 | | ||
Line 22: | Line 23: | ||
==== Modbus registers map ==== | ==== Modbus registers map ==== | ||
+ | There are 1000 HR registers available for the user, some of them are reserverd for special functions: | ||
+ | ^Holding Registers^^ | ||
+ | | 000-999: (F-RAM) || | ||
+ | |||
^Discrete Inputs ^^ | ^Discrete Inputs ^^ | ||
- | |DI0..7| Digital input state 0..7| | + | |DI0 ~ 7| Digital input state 0 ~ 7| |
+ | |HR20 ~ 27| Digital filter. (DI 0 ~ 7)| | ||
^Coils ^^ | ^Coils ^^ | ||
|C0..7| Digital outputs 0..7| | |C0..7| Digital outputs 0..7| | ||
- | ^Holding Registers^^ | + | ^Safety state ^^ |
- | | 000-999: (F-RAM) || | + | |HR35| Keep previous outputs state after restaft, 0 - off, 1 - on| |
- | |000| countung input (DI 0) high | | + | |
- | |001| counting input (DI 0) low | + | ^Predictive maintenance registers^^ |
- | |002| countung input (DI 1) high | | + | |HR0 ~ HR14| countung input (DI 0 ~ 7) dw, high word comes first | |
- | |003| counting input (DI 1) low | | + | |HR60 ~ HR 74|DI 0 ~ 7 time on totalizers |
- | |...|| | + | |
- | |014| countung input (DI 7) high | | + | ^PWM for triac outputs^^ |
- | |015| counting input (DI 7) low | | + | |HR111 ~ 118 |DO1 ~ 8 PWM duty cycle | |
- | |020| digital filter. (DI 0) /* 0 - disable, 1 - enable | | + | * this option available for the SSR outputs |
- | |021| digital filter. (DI 1) | | + | |
- | |...|| | + | ^System^^ |
- | |027| digital filter. (DI 7) | | + | |
|030| power-ups counter | | |030| power-ups counter | | ||
|031| uptime in seconds (high)| | |031| uptime in seconds (high)| | ||
|032| uptime in seconds (low) | | |032| uptime in seconds (low) | | ||
- | ^Input Registers^^ | + | ^Temperatures |
- | |0| 1-Wire temperature 1 (-100° - sensor failed or not connected) | | + | |IR0 ~ IR31| 1-Wire temperature 1 (-1000° |
- | |1| 1-Wire temperature 2 | | + | |HR33 |
- | |2| 1-Wire temperature 3 | | + | |
- | |...|| | + | |
- | |...|| | + | |
- | |31| 1-Wire temperature 31 | | + | |
- | + | ||
- | 033 - number of 1-Wire | + | |
+ | ===== Auto enumeration for 1-Wire sensors ===== | ||
+ | Each DS18B20 has their own unique serial number. Using a special search algorithm, the Synapse finds and saves the enumeration scheme for the sensors found in the static memory. New sensors still can be added to the existing enumeration by | ||
+ | *powering on or resetting the module | ||
+ | *writing non-zero value into HR33 register | ||
==== Modbus map csv-file ==== | ==== Modbus map csv-file ==== | ||
For the convinence, a module register map is provided from this {{synapse_all_reg_1wire.zip | link }} to import in the WebHMI project. | For the convinence, a module register map is provided from this {{synapse_all_reg_1wire.zip | link }} to import in the WebHMI project. | ||
+ | |||
+ | ==== Documentaion ==== | ||
+ | <WRAP center round download 60%> | ||
+ | {{syn_quick_guide_rev9_eng.pdf|Synapse Quick Guide Eng.}} | ||
+ | </ | ||
+ | |||
+ | |||
+ | |||
synapse.txt · Last modified: 2024/02/01 14:52 by emozolyak