 ====== Synapse remote I/O module ====== ====== Synapse remote I/O module ======
  
-{{ ::synapse_small.png?direct&200| 7bit Synapse remote I/O module}}+{{ ::syn_1wire.jpg?direct&200| 7bit Synapse remote I/O module}}
  
 The Synapse module (further reffered to as 'module') is produced under 7bit trademark and designed for data aquisition from discrete sensors and 1-Wire temperature sensors, as well as load control with digital outputs. The Synapse module (further reffered to as 'module') is produced under 7bit trademark and designed for data aquisition from discrete sensors and 1-Wire temperature sensors, as well as load control with digital outputs.
Line 22: Line 22:
  
 ==== Modbus registers map ==== ==== Modbus registers map ====
- +^Discrete Inputs ^^ 
-**Discrete Inputs**: DI 0-+|DI0..7| Digital input state 0..7| 
-**Coils**: DO 0-+^Coils ^^ 
- +|C0..7| Digital outputs 0..7| 
-**Holding Registers**: 0-999 +^Holding Registers^^ 
-000-999: (F-RAM) +000-999: (F-RAM) || 
-000 countung input (DI 0) high +|000countung input (DI 0) high | 
-001 counting input (DI 0) low  +|001counting input (DI 0) low  | 
-002 countung input (DI 1) high +|002countung input (DI 1) high | 
-003 counting input (DI 1) low  +|003counting input (DI 1) low | 
-... +|...|| 
-014 countung input (DI 7) high +|014countung input (DI 7) high | 
-015 counting input (DI 7) low  +|015counting input (DI 7) low  | 
- +|020digital filter. (DI 0)   /* 0 - disable, 1 - enable | 
-020 digital filter. (DI 0)   /* 0 - disable, 1 - enable +|021digital filter. (DI 1)  | 
-021 digital filter. (DI 1)   +|...|| 
-... +|027digital filter. (DI 7)  | 
-027 digital filter. (DI 7)   +|030power-ups counter | 
- +|031uptime in seconds (high)| 
-030 power-ups counter  +|032uptime in seconds (low) | 
-031 uptime in seconds (high) +^Input Registers^^ 
-032 uptime in seconds (low) +|01-Wire temperature 1 (-100° - sensor failed or not connected) | 
- +|11-Wire temperature 2 | 
-**Input Registers**:  +|21-Wire temperature 3 | 
-1-Wire temperature 1 (-100° - sensor failed or not connected) +|...|| 
-1-Wire temperature 2 +|...|| 
-1-Wire temperature 3 +|311-Wire temperature 31 |
-... +
-... +
-31 1-Wire temperature 31+
  
 033 - number of 1-Wire sensors on the bus, writing '0' - resets sensors enumeration tree and makes new enumaration, old sensors will be deleted, writing any number but '0' - leaves old enumaration tree and appends new sensors to the end 033 - number of 1-Wire sensors on the bus, writing '0' - resets sensors enumeration tree and makes new enumaration, old sensors will be deleted, writing any number but '0' - leaves old enumaration tree and appends new sensors to the end