synapse
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revisionNext revision | Previous revisionNext revisionBoth sides next revision | ||
synapse [2019/01/04 11:50] – emozolyak | synapse [2021/07/20 13:53] – [Modbus registers map] emozolyak | ||
---|---|---|---|
Line 1: | Line 1: | ||
====== Synapse remote I/O module ====== | ====== Synapse remote I/O module ====== | ||
- | {{ ::synapse_small.png? | + | {{ ::syn_1wire.jpg? |
The Synapse module (further reffered to as ' | The Synapse module (further reffered to as ' | ||
- | The module has 2 Ethernet interfaces (working in a " | + | The module has 2 Ethernet interfaces (working in a " |
+ | & MQTT protocols**. The enclosure | ||
+ | |||
+ | ==== Specifications ==== | ||
^^^ | ^^^ | ||
|Power: | 220VAC | | |Power: | 220VAC | | ||
Line 12: | Line 16: | ||
|Counter inputs (non-volitile) | 8 (digital inputs can be counting inputs with max. frequency of 1kHz, with anti-jitter filter of a 1ms step ) | | |Counter inputs (non-volitile) | 8 (digital inputs can be counting inputs with max. frequency of 1kHz, with anti-jitter filter of a 1ms step ) | | ||
|Digital Outputs| (2 groups x 4 outputs (symistor or relay ))2A | | |Digital Outputs| (2 groups x 4 outputs (symistor or relay ))2A | | ||
- | |1Wire bus | up to 32 sensors, cable length up tup 200 мeters | | + | |1Wire bus | up to 32 sensors, cable length up to 200 мeters | |
|Power supply for 'dry contacts' | |Power supply for 'dry contacts' | ||
|Enclosure protection | IP40 | | |Enclosure protection | IP40 | | ||
Line 18: | Line 22: | ||
|Weight: | 240 g. | | |Weight: | 240 g. | | ||
- | For the convinence, a module register map is provided | + | ==== Modbus registers map ==== |
+ | There are 1000 HR registers available for the user, some of them are reserverd for special functions: | ||
+ | ^Holding Registers^^ | ||
+ | | 000-999: (F-RAM) || | ||
+ | |||
+ | ^Discrete Inputs ^^ | ||
+ | |DI0 ~ 7| Digital input state 0 ~ 7| | ||
+ | |HR20 ~ 27| Digital filter. (DI 0 ~ 7)| | ||
+ | |||
+ | ^Coils ^^ | ||
+ | |C0..7| Digital outputs 0..7| | ||
+ | ^Safety state ^^ | ||
+ | |HR35| Keep previous outputs state after restaft, 0 - off, 1 - on| | ||
+ | |||
+ | ^Predictive maintenance registers^^ | ||
+ | |HR0 ~ HR14| countung input (DI 0 ~ 7) dw, high word comes first | | ||
+ | |HR60 ~ HR 74|DI 0 ~ 7 time on totalizers | | ||
+ | |||
+ | ^PWM for triac outputs^^ | ||
+ | |HR111 ~ 118 |DO1 ~ 8 PWM duty cycle | | ||
+ | * this option available for the SSR outputs | ||
+ | |||
+ | ^System^^ | ||
+ | |030| power-ups counter | | ||
+ | |031| uptime in seconds (high)| | ||
+ | |032| uptime in seconds (low) | | ||
+ | ^Temperatures ^^ | ||
+ | |IR0 ~ IR31| 1-Wire temperature 1 (-1000° - sensor failed or not connected) | | ||
+ | |HR33| Total sensors quantity / Init** (writing 0 to HR33 clears the enumeration.)| | ||
+ | |||
+ | **Auto enumeration for 1-Wire sensors**. Each DS18B20 has their own unique serial | ||
+ | number. Using a special search algorithm, the Synapse finds and saves the enumeration scheme for the sensors found in the static memory. New sensors still can be added to the existing enumeration by | ||
+ | *powering on or resetting the module | ||
+ | *writing non-zero value into HR33 register | ||
+ | |||
+ | ==== Modbus map csv-file ==== | ||
+ | For the convinence, a module register map is provided | ||
+ | |||
+ | ==== Documentaion ==== | ||
+ | <WRAP center round download 60%> | ||
+ | {{syn_quick_guide_rev9_eng.pdf|Synapse Quick Guide Eng.}} | ||
+ | </ | ||
+ | |||
+ | |||
+ | |||
synapse.txt · Last modified: 2024/02/01 14:52 by emozolyak