powtran
Differences
This shows you the differences between two versions of the page.
Next revision | Previous revision | ||
powtran [2019/01/08 13:41] – created emozolyak | powtran [2022/01/14 22:16] (current) – ↷ Links adapted because of a move operation 127.0.0.1 | ||
---|---|---|---|
Line 3: | Line 3: | ||
The Powtran model 9130A is used to show WebHMI connection example over RS-485. | The Powtran model 9130A is used to show WebHMI connection example over RS-485. | ||
- | {{ :: | + | {{ network: |
The drives have default protocol option that needs to be changed to " | The drives have default protocol option that needs to be changed to " | ||
Line 10: | Line 10: | ||
^::: | 1 - standard Modbus | ^::: | 1 - standard Modbus | ||
- | Для настройки возможности задания частоты по интерфейсу необходимо выставить источник в параметре | + | With right protocol setting it is possible to control the drive with these parameters: |
+ | |||
+ | ^ Pr. F0.03| = 9 (Frequency source) | | ||
+ | ^ Pr. F0.03| = 2 or 3 or 4 (run/stop source) | | ||
+ | ^ Modbus register 1000h (HR4096)| Write -10000..+10000 corresponding to -100.00% + 100.00% of rated drive frequency | | ||
+ | ^ Modbus register 2000h (HR8192)| Write 1 (run forward), 2 (run backward), 6 - stop with deceleration time | | ||
+ | ^ Modbus | ||
- | 1000h (адрес задается в свойствах регистра как HR4096)- для задания частоты вращения в Гц, путем записи значения -10000..+10000 что соответствует -100.00% + 100.00% номинальной частоты вращения ПЧ(реальная скорость вращения будет зависеть от числа полюсов двигателя), | ||
- | 2000h (адрес задается в свойствах регистра как HR8192)) - для задания команды запуск вперед(1), | ||
- | Также будет отображаться фактическая частота вращения из параметра 1001h (адрес HR4097). |