====== Connecting to Danfoss ERC-213 ====== | ====== Connecting to Danfoss ERC-213 ====== | ||
- | {{ :: | + | {{ network: |
These controllers supports Modbus RTU protocol starting from 4.16 version. | These controllers supports Modbus RTU protocol starting from 4.16 version. | ||
- | Особенности подключения: | + | Connection features: |
*fixed communication settings 9600 8, Еven, 1 | *fixed communication settings 9600 8, Еven, 1 | ||
*there is TTL tranceiver on-board, so it requires a special TTL-485 adapter. | *there is TTL tranceiver on-board, so it requires a special TTL-485 adapter. | ||
*TTL RX - line has a high driving requirement of more than 50 mA, some " | *TTL RX - line has a high driving requirement of more than 50 mA, some " |