 ====== Connecting to Delta Variable Frequency Drives ====== ====== Connecting to Delta Variable Frequency Drives ======
  
-{{ ::c2000_photo.jpg?direct&200|}}+{{ network:c2000_photo.jpg?direct&200|}}
  
 All Delta Electronics frequency converters of different series have almost the same parameter sets related to Modbus communication. This article uses the CP2000 model as an example. (in other models, some parameters may be missing or have other addresses, but in general the settings are identical) All Delta Electronics frequency converters of different series have almost the same parameter sets related to Modbus communication. This article uses the CP2000 model as an example. (in other models, some parameters may be missing or have other addresses, but in general the settings are identical)
Line 17: Line 17:
 There is a special VFD control & status memory area, described in the same chapter as group #9: There is a special VFD control & status memory area, described in the same chapter as group #9:
  
-{{ ::delta_vfd_regs.png?direct&600 |}}+{{ network:delta_vfd_regs.png?direct&600 |}}
  
 So, to run/stop the drive you can do the following: So, to run/stop the drive you can do the following:
Line 23: Line 23:
   *create a register with Modbus address HR2000 and bit mask selecting 4 least bits   *create a register with Modbus address HR2000 and bit mask selecting 4 least bits
      
-{{::register_mask.png?direct|}}+{{network:register_mask.png?direct|}}
  
   *create maintained button on the dashboard which would write 2/1 values upon press/release to run/stop the dirve respectively    *create maintained button on the dashboard which would write 2/1 values upon press/release to run/stop the dirve respectively 
  
-{{ ::delta_dash_control.png?direct&500 |}}+{{ network:delta_dash_control.png?direct&500 |}}
  