 ====== Controlling Danfoss frequency drives ====== ====== Controlling Danfoss frequency drives ======
  
-{{ ::​fc51_picture_eng.jpg?​direct&​400|}}+{{ ::​fc51_picture_eng.jpg?​direct&​300|}}
 Danfoss frequency drives supports Modbus protocol. To enable it, the parameter 08-30 should be set to [2]. Danfoss frequency drives supports Modbus protocol. To enable it, the parameter 08-30 should be set to [2].
  
Line 28: Line 28:
 To access any paramter you can use the formula: (Pr.Num. * 10 - 1). E.g. 8-31 (bus address) will equal 831*10 - 1 = 8309. To access any paramter you can use the formula: (Pr.Num. * 10 - 1). E.g. 8-31 (bus address) will equal 831*10 - 1 = 8309.
  
-{{ ::​fc51_reg_setup_1.png?​direct&​600 ​|}}+{{ ::​fc51_reg_setup_1.png?​direct |}}
  
 Below are the register settings for controlling the VLT Micro drive FC51 frequency converter - start / stop, change of direction of rotation, speed reference. Below are the register settings for controlling the VLT Micro drive FC51 frequency converter - start / stop, change of direction of rotation, speed reference.
  
-{{ ::​fc51_reg_setup_2.png?​direct&​600 ​|}}+{{ ::​fc51_reg_setup_2.png?​direct |}}
  
 In the frequency converter, the frequency values are presented as follows: the frequency 50 Hz (100% of the scale) corresponds to the number 16384. Negative values are also a number in binary complementary form (two's complement). Therefore, to correctly display the frequency and its task for the registers, it is necessary to use the multiplier 50/16384 = 0.0030517578125,​ and specify the appropriate format in the register properties. In the frequency converter, the frequency values are presented as follows: the frequency 50 Hz (100% of the scale) corresponds to the number 16384. Negative values are also a number in binary complementary form (two's complement). Therefore, to correctly display the frequency and its task for the registers, it is necessary to use the multiplier 50/16384 = 0.0030517578125,​ and specify the appropriate format in the register properties.