====== Controlling Danfoss frequency drives ====== | ====== Controlling Danfoss frequency drives ====== | ||
- | {{ :: | + | {{ network: |
- | Danfoss frequency drives supports Modbus protocol. To enable it, the parameter 08-30 should be set to '2'. | + | Danfoss frequency drives supports Modbus protocol. To enable it, the parameter 08-30 should be set to [2]. |
Other communication parameters are in the same 8th group: | Other communication parameters are in the same 8th group: | ||
Line 20: | Line 20: | ||
***REF** Bus reference register - frequency setpoint HR50009 | ***REF** Bus reference register - frequency setpoint HR50009 | ||
***STW** status word - accessible bitwise on C32..C47 addresses with Read coils or HR50199 with holding register read | ***STW** status word - accessible bitwise on C32..C47 addresses with Read coils or HR50199 with holding register read | ||
- | **MAV** actual frequency HR50209. | + | |
More details on working with Danfoss FC drives are described in document MG.02.A4.02 VLT® Micro Drive FC 51 Operating Instructions. Below is a table with parameters. The parameter numbers specified in these tables must be specified in the register settings with an offset of -1. For example, the Bus reference register (REF) in the documentation has the address 50000, but in the WebHMI you set it as HR49999. | More details on working with Danfoss FC drives are described in document MG.02.A4.02 VLT® Micro Drive FC 51 Operating Instructions. Below is a table with parameters. The parameter numbers specified in these tables must be specified in the register settings with an offset of -1. For example, the Bus reference register (REF) in the documentation has the address 50000, but in the WebHMI you set it as HR49999. | ||
- | {{:: | + | {{network: |
To access any paramter you can use the formula: (Pr.Num. * 10 - 1). E.g. 8-31 (bus address) will equal 831*10 - 1 = 8309. | To access any paramter you can use the formula: (Pr.Num. * 10 - 1). E.g. 8-31 (bus address) will equal 831*10 - 1 = 8309. | ||
- | {{ :: | + | {{ network: |
Below are the register settings for controlling the VLT Micro drive FC51 frequency converter - start / stop, change of direction of rotation, speed reference. | Below are the register settings for controlling the VLT Micro drive FC51 frequency converter - start / stop, change of direction of rotation, speed reference. | ||
- | {{ :: | + | {{ network: |
In the frequency converter, the frequency values are presented as follows: the frequency 50 Hz (100% of the scale) corresponds to the number 16384. Negative values are also a number in binary complementary form (two's complement). Therefore, to correctly display the frequency and its task for the registers, it is necessary to use the multiplier 50/16384 = 0.0030517578125, | In the frequency converter, the frequency values are presented as follows: the frequency 50 Hz (100% of the scale) corresponds to the number 16384. Negative values are also a number in binary complementary form (two's complement). Therefore, to correctly display the frequency and its task for the registers, it is necessary to use the multiplier 50/16384 = 0.0030517578125, | ||
- | По [[ https:// | + | There is a [[ https:// |
- | {{:: | + | {{network: |