- | {{ :: | + | {{ network: |
- | Danfoss frequency drives supports Modbus protocol. To enable it, the parameter 08-30 should be set to '2'. | + | Danfoss frequency drives supports Modbus protocol. To enable it, the parameter 08-30 should be set to [2]. |
Other communication parameters are in the same 8th group: | Other communication parameters are in the same 8th group: | ||
Line 9: | Line 9: | ||
*8-33 Parity and stop bit [0..3] ( Even, 1 stop; Odd, 1 stop ;No parity, 1 stop; No parity, 2) | *8-33 Parity and stop bit [0..3] ( Even, 1 stop; Odd, 1 stop ;No parity, 1 stop; No parity, 2) | ||
- | При изменении протокола обмена, преобразователь требуется перезапустить (переподключить питание). Также в момент изменения протокола c FC 8-30[0] | + | After changing protocol type, it neccessary to re-power the drive. Also, with changing protocol |
- | Управление приводом производится через: | + | |
- | слово управления (CTW) - пуск, стоп, выбор конфигурации и др. Оно доступно по адресам C0..C15 через функцию Read coils, либо HR49999 через функцию чтения holding register | + | The drive can only be controll via Modbus when it is switched from Hand to Auto mode. |
- | задание частоты через Bus reference register (REF) по адресу HR50009 | + | |
- | контроль состояния - через слово статуса STW - C32..C47 , либо HR50199 | + | |
- | фактическая частота вращения (MAV) по адресу HR50209. | + | |
- | Подробно работа с ПЧ Danfoss описана в документе MG.02.A4.02 VLT® Micro Drive FC 51 Operating Instructions. Ниже приведена таблица с параметрами. Номера параметров, | + | |
- | {{:: | + | There might be a case, when actual frequency differs from the setpoint by a certain level. |
- | Для модификации произвольного параметра преобразователя частоты, | + | The drive is controled and monitored via: |
- | {{ :: | + | ***CTW** control word - start, stop, configuration etc. accessible bitwise on C0..C15 addresses with Read coils or HR49999 with holding register read |
+ | ***REF** Bus reference register - frequency setpoint HR50009 | ||
+ | ***STW** status word - accessible bitwise on C32..C47 addresses with Read coils or HR50199 with holding register read | ||
+ | ***MAV** actual frequency HR50209. | ||
- | Ниже приведены настройки регистров для управления преобразователем частоты VLT Micro drive FC51 - пуск / останов, смена направления вращения, задание частоты вращения. | + | More details on working with Danfoss FC drives are described in document MG.02.A4.02 VLT® Micro Drive FC 51 Operating Instructions. Below is a table with parameters. The parameter numbers specified in these tables must be specified in the register settings with an offset of -1. For example, the Bus reference register (REF) in the documentation has the address 50000, but in the WebHMI you set it as HR49999. |
- | {{ :: | + | |
- | В частотном преобразователе значения частоты представлены следующим образом - частоте 50Гц (100% шкалы) соответствует число 16384. Отрицательным значениям - тоже число в двоичном дополненном виде (two's complement). Поэтому для правильного отображения частоты и ее задания для регистров необходимо использовать множитель 50/16384 = 0.0030517578125, | + | {{network: |
- | По [[ https:// | + | To access any paramter you can use the formula: (Pr.Num. * 10 - 1). E.g. 8-31 (bus address) will equal 831*10 - 1 = 8309. |
- | {{:: | + | |
+ | {{ network: | ||
+ | |||
+ | Below are the register settings for controlling the VLT Micro drive FC51 frequency converter - start / stop, change of direction of rotation, speed reference. | ||
+ | |||
+ | {{ network: | ||
+ | |||
+ | In the frequency converter, the frequency values are presented as follows: the frequency 50 Hz (100% of the scale) corresponds to the number 16384. Negative values are also a number in binary complementary form (two's complement). Therefore, to correctly display the frequency and its task for the registers, it is necessary to use the multiplier 50/16384 = 0.0030517578125, | ||
+ | |||
+ | There is a [[ https:// | ||
+ | {{network: | ||