====== Controlling Danfoss frequency drives ====== | ====== Controlling Danfoss frequency drives ====== | ||
- | {{ :: | + | {{ :: |
Danfoss frequency drives supports Modbus protocol. To enable it, the parameter 08-30 should be set to [2]. | Danfoss frequency drives supports Modbus protocol. To enable it, the parameter 08-30 should be set to [2]. | ||
Line 28: | Line 28: | ||
To access any paramter you can use the formula: (Pr.Num. * 10 - 1). E.g. 8-31 (bus address) will equal 831*10 - 1 = 8309. | To access any paramter you can use the formula: (Pr.Num. * 10 - 1). E.g. 8-31 (bus address) will equal 831*10 - 1 = 8309. | ||
- | {{ :: | + | {{ :: |
Below are the register settings for controlling the VLT Micro drive FC51 frequency converter - start / stop, change of direction of rotation, speed reference. | Below are the register settings for controlling the VLT Micro drive FC51 frequency converter - start / stop, change of direction of rotation, speed reference. | ||
- | {{ :: | + | {{ :: |
In the frequency converter, the frequency values are presented as follows: the frequency 50 Hz (100% of the scale) corresponds to the number 16384. Negative values are also a number in binary complementary form (two's complement). Therefore, to correctly display the frequency and its task for the registers, it is necessary to use the multiplier 50/16384 = 0.0030517578125, | In the frequency converter, the frequency values are presented as follows: the frequency 50 Hz (100% of the scale) corresponds to the number 16384. Negative values are also a number in binary complementary form (two's complement). Therefore, to correctly display the frequency and its task for the registers, it is necessary to use the multiplier 50/16384 = 0.0030517578125, |