Connecting to Siemens S7-300 PLC
The Iso-Over-TCP procotol is used for connection to the PLC, see Connecting to 1200 for reference.
Input correct TSAP number in the WebHMI connection settings:
- for CPU with built-in Ethernet port use TSAP number 0200, 0301
- for CPU without Ethernet port and CP343-1 Ethernet communication module use TSAP number 0302