 ====== Connecting to S7-1200 ====== ====== Connecting to S7-1200 ======
 +{{ :s7-1200.jpg?nolink&200|}}
 +It is possible to connect to the Siemens 1200 series controllers using the ISO-on-TCP protocol. To do this, several additional settings must be made in the controller configuration. To activate the S7 Communication operation mode in TIA Portal, the PLC must be configured correctly.
  
----- +==== Change protection options in the CPU settings ====
- +
-{{  ::protection_checkboxes_new.png?direct&600 |}} +
- +
-It is possible to connect to the Siemens 1200 series controllers using the ISO-on-TCP protocol. To do this, several additional settings must be made in the controller configuration. To activate the S7 Communication operation mode in TIA Portal, the PLC must be configured correctly:+
  
 1. Allow GET / PUT commands from third-party partners (in firmware revisions of S7-1200 lower than 4th version, these commands are allowed by default). 1. Allow GET / PUT commands from third-party partners (in firmware revisions of S7-1200 lower than 4th version, these commands are allowed by default).
 2. Enable Full Access in "Protection PLC" settings. 2. Enable Full Access in "Protection PLC" settings.
-{{ ::permit_access_put-get.png?direct|}}+ 
 +{{  ::protection_checkboxes_new.png?direct&600 |}}
  
 3. Disable Optimized Block Access for the Data Blocks you are going to exchange with.  3. Disable Optimized Block Access for the Data Blocks you are going to exchange with. 