 +====== BACnet IP ======
 +
 +{{::​internal-bacnet.png?​direct&​250|}}  ​
 +
 +Since version 3.0, WebHMI supports the BACnet IP protocol.
 +
 +For the moment, the Read Property and Write Property queries have been implemented. The Present Value properties are read. Such types of registers are read and written:
 +
 +  *Analog Input
 +  *Analog Output
 +  *Analog Value
 +  *Binary Input
 +  *Binary Output
 +  *Binary Value
 +  *Multi State Input
 +  *Multi State Output
 +  *Multi State Value
 +
 +In WebHMI, such addressing of BACnet IP registers is accepted:
 +^Register address ^Description ^Data type ^Read/​Write^
 +|AIxx |Analog Input. xx — input number (valid values from 0 to 65535). Examples: AI1, AI12, AI44 |Double Word, Float, 32 IEEE 754 |Read/​-|
 +|AOxx.yy |Analog Output. xx — output number(valid value range 0..65535). Example: AO1, AO12, AO44.2, AO23.17. yy — write priority, see below |Double Word, Float, 32 IEEE 754 |Read/​Write|
 +|AVxx.yy |Analog Value. xx — value number (valid value range 0..65535). Example: AV1, AV12, AV44.2, AV23.17. yy — write priority, см. ниже |Double Word, Float, 32 IEEE 754 |Read/​Write|
 +|BIxx |Binary Input. xx — input number(valid range 0..65535). Examples: BI1, BI12, BI44 |Bit |Read/​-|
 +|BOxx.yy |Binary Output. xx — output number (valid range 0..65535). Examples: BO1, BO12, BO44.2, BO23.17. yy — write priority, см. ниже |Bit |Read/​Write|
 +|BVxx.yy |Binary Value. xx — value number (valid range 0..65535). Examples: BV1, AV12, BV44.2, BV23.17. yy — write priority, см. ниже |Bit|Read/​Write|
 +|MIxx |Multi State Input. xx — input number(valid range 0..65535). Examples: MI1, MI12, MI44 |Byte, Unsigned Int|Read/-|
 +|MOxx.yy |Multi State Output. xx — output number(valid range 0..65535). Examples: MO1, MO12, MO44.2, MO23.17. yy — write priority, см. ниже |Byte,​ Unsigned Int|Read/​Write|
 +|MVxx.yy |Multi State Value. xx — output number(valid range 0..65535). Examples: MV1, MV12, MV44.2, MV23.17. yy — write priority, см. ниже |Byte,​ Unsigned Int|Read/​Write|
 +
 +When writing new values ​​to registers with missing '​.yy'​ in the register'​s address the default priority is used. Example of such address: AI22
 +If you specify a number from 1 to 16 after the point, for example AI22.9, then writing to the register will occur with the specified priority. In this example, this will be 9.
 +
 +If you want to organize writing with the priority NULL, then in the register address you need to specify the number 17. Example AI22.17.
  