bacnet
no way to compare when less than two revisions
Differences
This shows you the differences between two versions of the page.
Next revision | |||
— | bacnet [2019/01/09 14:17] – created emozolyak | ||
---|---|---|---|
Line 1: | Line 1: | ||
+ | ====== BACnet IP ====== | ||
+ | |||
+ | {{:: | ||
+ | |||
+ | Since version 3.0, WebHMI supports the BACnet IP protocol. | ||
+ | |||
+ | For the moment, the Read Property and Write Property queries have been implemented. The Present Value properties are read. Such types of registers are read and written: | ||
+ | |||
+ | *Analog Input | ||
+ | *Analog Output | ||
+ | *Analog Value | ||
+ | *Binary Input | ||
+ | *Binary Output | ||
+ | *Binary Value | ||
+ | *Multi State Input | ||
+ | *Multi State Output | ||
+ | *Multi State Value | ||
+ | |||
+ | In WebHMI, such addressing of BACnet IP registers is accepted: | ||
+ | ^Register address ^Description ^Data type ^Read/ | ||
+ | |AIxx |Analog Input. xx — input number (valid values from 0 to 65535). Examples: AI1, AI12, AI44 |Double Word, Float, 32 IEEE 754 |Read/ | ||
+ | |AOxx.yy |Analog Output. xx — output number(valid value range 0..65535). Example: AO1, AO12, AO44.2, AO23.17. yy — write priority, see below |Double Word, Float, 32 IEEE 754 |Read/ | ||
+ | |AVxx.yy |Analog Value. xx — value number (valid value range 0..65535). Example: AV1, AV12, AV44.2, AV23.17. yy — write priority, см. ниже |Double Word, Float, 32 IEEE 754 |Read/ | ||
+ | |BIxx |Binary Input. xx — input number(valid range 0..65535). Examples: BI1, BI12, BI44 |Bit |Read/ | ||
+ | |BOxx.yy |Binary Output. xx — output number (valid range 0..65535). Examples: BO1, BO12, BO44.2, BO23.17. yy — write priority, см. ниже |Bit |Read/ | ||
+ | |BVxx.yy |Binary Value. xx — value number (valid range 0..65535). Examples: BV1, AV12, BV44.2, BV23.17. yy — write priority, см. ниже |Bit|Read/ | ||
+ | |MIxx |Multi State Input. xx — input number(valid range 0..65535). Examples: MI1, MI12, MI44 |Byte, Unsigned Int|Read/-| | ||
+ | |MOxx.yy |Multi State Output. xx — output number(valid range 0..65535). Examples: MO1, MO12, MO44.2, MO23.17. yy — write priority, см. ниже |Byte, | ||
+ | |MVxx.yy |Multi State Value. xx — output number(valid range 0..65535). Examples: MV1, MV12, MV44.2, MV23.17. yy — write priority, см. ниже |Byte, | ||
+ | |||
+ | When writing new values to registers with missing ' | ||
+ | If you specify a number from 1 to 16 after the point, for example AI22.9, then writing to the register will occur with the specified priority. In this example, this will be 9. | ||
+ | |||
+ | If you want to organize writing with the priority NULL, then in the register address you need to specify the number 17. Example AI22.17. | ||