Last revisionBoth sides next revision
ap-metering [2022/05/10 08:48] – created emozolyakap-metering [2022/11/07 11:05] – [M-bus protocol] emozolyak
Line 2: Line 2:
  
 This version of the AirPoint module is intended for reading data from heat meters via the M-bus protocol and transmitting telemetry data via the MQTT protocol to data collection systems. This version of the AirPoint module is intended for reading data from heat meters via the M-bus protocol and transmitting telemetry data via the MQTT protocol to data collection systems.
 +
 +{{ :conn:conn-examples:ap-m-app-structure2.png?direct&600 |}}
 +===== Features =====
 +  *Compatible meters: DIEHL Scylar INT, Siemens FUE950, Danfoss Infocal, and their equivalents
 +  *Connection using a standard connector (included with the module) instead of the communication board of the heat meter
 +  *Energy saving polling cycle
 +
 +{{ :conn:conn-examples:scylar-picutre.png?direct&350 |}}
 +
 +
 +
 +
 +
 +===== Connection method =====
 +The module connects to a meter with edge connector right to the extension module slot.
 +
 +{{ ::metering_option.jpg?direct&400 |}}
 +
 +==== M-bus protocol  ====
 +All meters are read with "REQ-UD2" request using broadcast address. The M-bus tags are mapped onto statndard AirPoint's MQTT topics: 
 +^ Value     Description   ^ Units ^ Mapped to ^
 +|FWT      | Forward temp.  |  °C   | "temp_int"    |
 +|RET      | Return temp.    °C   | "temp_ext"    |
 +|E        | Energy         | Gcal| "counter_in1" |
 +|VOL      | Volume           m3  | "counter_in2" |
 +|Q        | Flow  |  m3/hour   | "hum_int"     |
 +
  