- | Диспетчеризация и удаленное управление холодильным оборудованием становится все актуальнее. Вовремя отследить неисправность, | + | Increasing demand for the refrigeration quality |
- | Ak-cc 550 картинка.png | + | For now, almost every vendor for the cooling equipment provides web-based solution for monitoring and control, but |
- | Контроллеры холодильного оборудования Danfoss AK-CC 550 имеет особенности реализации коммуникационного интерфейса: | + | their main drawback is that they focused only on their cooling controllers |
- | автонастройку на скорость опроса, | + | With only one WebHMI |
- | фиксированный формат передачи байта - старт-бит, | + | |
- | Параметры прибора в руководстве пользователя имеют буквенно-цифровой код, например r14, u11. Эти коды точно также отображаются на индикаторе прибора. Сетевой адрес модуля выставляется в параметре о03. Для получения Modbus адреса параметра необходимо определить его PNU номер (Parameter number) и вычесть из него 1. Полный перечень параметров и соответствующих PNU номеров приведен в документе AK-CC550 Modbus Parameter Definitions. Данный документ доступен по запросу [info@webhmi.com.ua]. Фрагмент таблицы параметров представлен ниже. | + | |
- | {{:: | + | Danfoss АК-СС 550 refrigeration controllers are very popular devices applied in industrial cooling units, with some features of communication over Modbus: |
+ | |||
+ | * autosetup for baud rate - i.e. after the module detect 3 polls not matching own communication speed, it will change own uart's transmission rate to next option [9600, 19200, 38400]. | ||
+ | * fixed data format - start bit, 8 data bits, parity bit (even), 1 stop bit | ||
+ | |||
+ | The module parameters in the user manual have an alphanumeric code, for example r14, u11. These codes are also displayed on the instrument display. The network address of the module is set in parameter o03. To obtain a Modbus parameter address, one have to subtract 1 from PNU number (Parameter number). A complete list of parameters and the corresponding PNU numbers is given in AK-CC550 Modbus Parameter Definitions document. This document is available on request . A fragment of the parameter table is presented below. | ||
+ | |||
+ | {{ network: | ||
There is a [[ https:// | There is a [[ https:// | ||
- | {{:: | + | {{ network: |