 ====== Connecting to cooling controller Danfoss AK-CC 550 ====== ====== Connecting to cooling controller Danfoss AK-CC 550 ======
  
-{{ ::ak-cc_550_pic.png?direct&300|}}+{{ network:ak-cc_550_pic.png?direct&300|}}
  
 Increasing demand for the refrigeration quality ( keeping optimal product storage temperature) and efficiency (minimizing power consumption) enforces introduction of the scada/monitoring systems which would helped to track malfanctions in time, detect abnormal situation and operation modes, provide analityics for resousrce consumption, or even optimize resource consumption using different strategies.  Increasing demand for the refrigeration quality ( keeping optimal product storage temperature) and efficiency (minimizing power consumption) enforces introduction of the scada/monitoring systems which would helped to track malfanctions in time, detect abnormal situation and operation modes, provide analityics for resousrce consumption, or even optimize resource consumption using different strategies. 
Line 15: Line 15:
   * fixed data format - start bit, 8 data bits, parity bit (even), 1 stop bit   * fixed data format - start bit, 8 data bits, parity bit (even), 1 stop bit
  
-Параметры прибора в руководстве пользователя имеют буквенно-цифровой коднапример r14, u11. Эти коды точно также отображаются на индикаторе прибораСетевой адрес модуля выставляется в параметре о03Для получения Modbus адреса параметра необходимо определить его PNU номер (Parameter number) и вычесть из него 1Полный перечень параметров и соответствующих PNU номеров приведен в документе AK-CC550 Modbus Parameter Definitions. Данный документ доступен по запросу [info@webhmi.com.ua]Фрагмент таблицы параметров представлен ниже.+The module parameters in the user manual have an alphanumeric codefor example r14, u11. These codes are also displayed on the instrument displayThe network address of the module is set in parameter o03To obtain a Modbus parameter address, one have to subtract 1 from PNU number (Parameter number). A complete list of parameters and the corresponding PNU numbers is given in AK-CC550 Modbus Parameter Definitions documentThis document is available on request A fragment of the parameter table is presented below.
  
-Instrument parameters in the user manual have an alphanumeric code, for example r14, u11. These codes are also displayed on the instrument display. The network address of the module is set in parameter o03. To obtain a Modbus parameter address, one have to subtract 1 from PNU number (Parameter number). A complete list of parameters and the corresponding PNU numbers is given in AK-CC550 Modbus Parameter Definitions. This document is available on request . A fragment of the parameter table is presented below. +{{ network:modbus_table_akcc.png?direct&600 |}}
- +
-{{ ::modbus_table_akcc.png?direct&600 |}}+
  
 There is a [[ https://www.youtube.com/watch?v=iU3dzC1dQ4E | video ]] (in Russian language) with live demo of controlling Danfoss AK-CC 550, and FCS 51 frequency drive as well. There is a [[ https://www.youtube.com/watch?v=iU3dzC1dQ4E | video ]] (in Russian language) with live demo of controlling Danfoss AK-CC 550, and FCS 51 frequency drive as well.
  
-{{ ::webhmi_fc51_aka550.jpg?direct&600 |}}+{{ network:webhmi_fc51_aka550.jpg?direct&600 |}}