The Synapse module (further reffered to as 'module') is produced under 7bit trademark and designed for data aquisition from discrete sensors and 1-Wire temperature sensors, as well as load control with digital outputs.
The module has 2 Ethernet interfaces (working in a “bridge” mode) for LAN connection and supports Modbus TCP & MQTT protocols. The enclosure is for panel / DIN 35 mm mount.
Power: | 220VAC |
Ethernet mode | DHCP client / static IP |
Digital Inputs | 8 (24Vdc) |
Counter inputs (non-volitile) | 8 (digital inputs can be counting inputs with max. frequency of 1kHz, with anti-jitter filter of a 1ms step ) |
Digital Outputs | (2 groups x 4 outputs (symistor or relay ))2A |
1Wire bus | up to 32 sensors, cable length up to 200 мeters |
Power supply for 'dry contacts' | yes |
Enclosure protection | IP40 |
Dimensions (HхWхD): | 145х90х40 mm. |
Weight: | 240 g. |
There are 1000 HR registers available for the user, some of them are reserverd for special functions:
Holding Registers | |
---|---|
000-999: (F-RAM) |
Discrete Inputs | |
---|---|
DI0 ~ 7 | Digital input state 0 ~ 7 |
HR20 ~ 27 | Digital filter. (DI 0 ~ 7) |
Coils | |
---|---|
C0..7 | Digital outputs 0..7 |
Safety state | |
HR35 | Keep previous outputs state after restaft, 0 - off, 1 - on |
Predictive maintenance registers | |
---|---|
HR0 ~ HR14 | countung input (DI 0 ~ 7) dw, high word comes first |
HR60 ~ HR 74 | DI 0 ~ 7 time on totalizers |
PWM for triac outputs | |
---|---|
HR111 ~ 118 | DO1 ~ 8 PWM duty cycle |
* this option available for the SSR outputs
System | |
---|---|
HR30 | power-ups counter |
HR31 | uptime in seconds (high) |
HR32 | uptime in seconds (low) |
Temperatures | |
---|---|
IR0 ~ IR31 | 1-Wire temperature 1 (-1000° - sensor failed or not connected) |
HR33 | Total sensors quantity or Init** (writing 0 to HR33 clears the enumeration) |
Each DS18B20 has their own unique serial number. Using a special search algorithm, the Synapse finds and saves the enumeration scheme for the sensors found in the static memory. New sensors still can be added to the existing enumeration by
For the convinence, a module register map is provided from this link to import in the WebHMI project.
In the v2, there were the following features added:
Please refer to the product page.