 7bit Synapse remote I/O module

The Synapse module (further reffered to as 'module') is produced under 7bit trademark and designed for data aquisition from discrete sensors and 1-Wire temperature sensors, as well as load control with digital outputs.

The module has 2 Ethernet interfaces (working in a “bridge” mode) for LAN connection and supports Modbus TCP & MQTT protocols. The enclosure is for panel / DIN 35 mm mount.

Specifications

Power: 220VAC
Ethernet mode DHCP client / static IP
Digital Inputs 8 (24Vdc)
Counter inputs (non-volitile) 8 (digital inputs can be counting inputs with max. frequency of 1kHz, with anti-jitter filter of a 1ms step )
Digital Outputs (2 groups x 4 outputs (symistor or relay ))2A
1Wire bus up to 32 sensors, cable length up to 200 мeters
Power supply for 'dry contacts' yes
Enclosure protection IP40
Dimensions (HхWхD): 145х90х40 mm.
Weight: 240 g.

Modbus registers map

There are 1000 HR registers available for the user, some of them are reserverd for special functions:

Holding Registers
000-999: (F-RAM)
Discrete Inputs
DI0 ~ 7 Digital input state 0 ~ 7
HR20 ~ 27 Digital filter. (DI 0 ~ 7)
Coils
C0..7 Digital outputs 0..7
Safety state
HR35 Keep previous outputs state after restaft, 0 - off, 1 - on
Predictive maintenance registers
HR0 ~ HR14 countung input (DI 0 ~ 7) dw, high word comes first
HR60 ~ HR 74DI 0 ~ 7 time on totalizers
PWM for triac outputs
HR111 ~ 118 DO1 ~ 8 PWM duty cycle

* this option available for the SSR outputs

System
HR30 power-ups counter
HR31 uptime in seconds (high)
HR32 uptime in seconds (low)
Temperatures
IR0 ~ IR31 1-Wire temperature 1 (-1000° - sensor failed or not connected)
HR33 Total sensors quantity or Init** (writing 0 to HR33 clears the enumeration)

Auto enumeration for 1-Wire sensors

Each DS18B20 has their own unique serial number. Using a special search algorithm, the Synapse finds and saves the enumeration scheme for the sensors found in the static memory. New sensors still can be added to the existing enumeration by

Modbus map csv-file

For the convinence, a module register map is provided from this link to import in the WebHMI project.

Documentaion

Synapse v2

In the v2, there were the following features added:

Please refer to the product page.