====== Modbus ====== {{network:modbus_logo.png?direct&250|}} In WebHMI, such syntax of addressing ModBus (RTU/ASCII/TCP) registers is defined: ^Register address ^Description ^Data type^ Read(FC((FC - function code used)))/Write(FC)^ |Cx |Coils. X — output number (valid range is 0..65535). Examples: C1, C3, C44 |Bit| Read(0x01)/Write(0x05)| |DIx |Discrete Inputs. X — input number (valid range 0 ..65535). Examples: DI1, DI3, DI44, DI45000 |Bit |Read(0x02)/—| |HRx |Holding Registers. X — register address (valid range 0..65535). Examples: HR1, HR3, HR44, HR65043 |Bit, Byte, Word, Double Word |Read(0x03)/Write(0x06)| |MHRx |Identical to HRx. The difference is that the writing in such registers occurs using the Modbus function No. 16 (Preset Multiple Register). |Bit, Byte, Word, Double Word |Read(0x03)/Write(0x16)| |IRx |Input Registers. X — register address (valid range 0..65535). Примеры: IR1, IR3, IR44, IR65043 |Bit, Byte, Word, Double Word |Read(0x04)/—| ATTENTION! By default, for double word reading, two queries each by one word will be used. To explicitly set double-word reading with one query (multiple read), you must enable grouping in the connection properties.